Take a Test Article Library CEEJ Home
Submit an Article
Contact CEEJ
Article # 0005
Burner
Management Systems
By Tom
Cox, P.E.
Introduction
The following paragraphs
outline a general method for
implementing a typical boiler Burner Management System (BMS). Several general
guidelines to implement operation strategies for such a system are also
provided.
This document is intended for
use by the control systems designer as
a guide for basic design. Final and detailed BMS design is required per
the applicable design specifications. This narrative contains provisions
required for compliance with the NFPA 8501 Standard for
Single Burner Operation. The control systems designer is responsible for
compliance with this standard, and all other applicable federal, state and local standards and regulations.
General
The Burner Management System
must be
designed to ensure a safe, orderly operating sequence in the
start-up and shutdown of fuel firing equipment and to reduce possible errors by following
the operating procedure.
The system is
intended to protect against malfunction of fuel firing equipment and associated systems.
The safety features of the system
shall be designed to provide protection in most common emergency situations, however,
the system cannot replace an intelligent operators reasonable judgment in all situations.
In some
phases of operation, the BMS shall provide permissive
interlocks only to insure safe startup of equipment. Once the
equipment is in service, the operator must follow acceptable safe
operating practices.
It is essential that all parts of the BMS are
in good working order and in
service whenever the burner is in service if the system is to provide the protection for which it is
designed. Regular maintenance and inspection of the system and
its associated hardware is essential for its continued safe operation.
This narrative gives a description of
a typical BMS as it relates to the various operating phases and
the operation of the fuel firing equipment and associated systems.
BMS Functions
The BMS shall be
designed to perform the following functions:
1. Prevent firing unless a satisfactory furnace purge
has first been completed.
2. Prohibit start-up
of the equipment unless
certain permissive interlocks have first been completed.
3.
Monitor and control the correct component sequencing during start-up and shut-down of
the equipment.
4.
Conditionally allow the continued operation of the equipment only while
certain safety interlocks remaining satisfied.
5. Provide component
condition feedback to the operator and, if so equipped, to the plant control systems and/or data loggers.
6. Provide
automatic supervision when the equipment is in
service and provide means to make a Master Fuel Trip (MFT) should certain
unacceptable firing conditions occur.
7.
Execute a MFT upon certain adverse unit
operating conditions.
Operation
Per NFPA 8501, section
2-1.3(b), a common cause of furnace explosions is “Fuel
leakage into an idle furnace and the ignition of the accumulation by a spark or
other source of ignition”. Proper attention to the design of the
interlocks and trip system to provide a safe light up of the boiler furnace is
required.
Furnace Purge
Before any fuel firing
is permitted,
either initially or after a boiler trip, a satisfactory furnace purge cycle must be completed. Prior to starting a furnace purge cycle, the operator must ensure
that the following purge requirements are satisfied[i]:
1. Drum level within operating range (not high, not low)
2. Instrument air header pressure
within operating range
3. Fan is in service
4. Purge airflow capable of a minimum of 70% of
the full load airflow established through the unit[ii].
5. All flame scanners reading "No Flame"
6. Natural gas block valves are proven closed
7. Fuel oil block valves are proven closed
8. Air dampers are in the fully open position
9. Natural gas, or fuel oil, header pressure upstream
of block valve is satisfactory
10. Pilot gas header pressure is satisfactory
11. Burner Control System is energized
12. A "No Master Fuel Trip condition" condition
is established
As each of the above conditions is
reached, their respective
indicator lights[iii]
shall illuminate as "PURGE PERMISSIVES" on the operator control console.
Once all of the above conditions are satisfied, the "PURGE
AVAILABLE" light shall illuminate indicating that the START PURGE
switch is enabled by the system logic. Activating the START PURGE control,
when the "PURGE AVAILABLE" light is illuminated, will begin a timed furnace purge cycle as
indicated by a "PURGE IN PROGRESS" light illuminating.
As indicated in NFPA
8501, section 6-2.4.1(i), the purge shall be “...sufficient for at least
eight air changes” of the furnace.
If the
operator is starting the boiler from the cold condition, or restarting
after a Master Fuel Trip event, the procedure outlined in the following
paragraphs is required. If the boiler is recycling or otherwise starting from a warm
condition, the MFT circuit will reset automatically and the procedure
will skip directly to the main flame light off sequence.
At the end of the purge cycle,
and providing that the purge
requirements remained satisfied, the damper control shall position the inlet
damper for light-off, approximately 10% to 30% airflow, depending on
burner design, required turn-down, etc. The "PURGE COMPLETE" light will
illuminate
and the boiler trip circuit shall be ready for reset, and so indicated by a "MFT
RESET" light.
Provided the start-up permissives remain satisfied, the system shall initiate a burner startup period timer set
for no more than 10 minutes. If the operator does not initiate a start-up
within this time, the boiler control system will exit the “PURGE COMPLETE”
condition and the operator must begin again with the pre-purge cycle. If
the MFT has been reset, the boiler control system will trip the MFT
when leaving the “PURGE COMPLETE” condition.
Upon
completing a satisfactory purge, the operator must press the “RESET MFT”
pushbutton. The boiler control system will indicate that the MFT has been reset
with a steady on “MFT RESET” light. At this point, the boiler control system is
ready to allow the main flame start-up sequence.
Main Flame Start-Up Sequence
The main flame start-up sequence,
from the lighting the of the pilot flame through main flame light-off, is an automated
sequence. Once the start-up sequence has begun, only the
“BOILER STOP” switch and the “EMERGENCY STOP” will interrupt the start-up
sequence. Any interruption of the start-up sequence requires a post-fire purge
prior to attempting to start the boiler again. To initiate the start-up sequence,
the operator activates the “START BOILER” switch.
Pilot Flame Light-Off
Before the burner can be started,
satisfactory light-off conditions for the pilot and main burners must be met.
This is
accomplished when the following conditions are satisfied:
For the pilot igniter:
1. MFT relay reset
2. Pilot gas header pressure normal
For
natural gas:
1. All of the above mentioned for the pilot igniter
2. Natural gas pressure normal
3. Natural gas control valve is in light-off position
For
fuel oil:
1. All of the above mentioned for the pilot igniter
2. Oil gun is in place in the burner
3. Oil pressure is normal
4. Fuel oil atomizing interlocks are satisfied
5. Fuel oil atomizing medium is provided to the burner
6. Oil control valve is in light-off position
Other Conditions:
1. No MFT condition after purge
2. All flame scanners report no flame
3. All natural gas,
or all fuel oil,
block valves shown closed
4. All air dampers are in light-off position
Failure to meet any of these conditions shall prevent the burner light-off operation.
To light the pilot flame,
the pilot header vent valve, and, for natural gas fuel, the natural gas vent
valve
shall be closed by the boiler control system. Then, sequentially, the igniter transformer is energized,
the pilot gas block
valves are open and a 10 second pilot ignition timer starts counting down. When ignition timer
cycle is completed, the igniter transformer is
de-energized and the pilot flame scanner is checked by the control system.
If the pilot flame is present, the main
flame light-off sequence continues.
If the pilot
flame fails, the boiler control system
initiates a pilot flame failure shutdown. Additional attempts of pilot light-off are
permissible provided a successful pilot light-off is made within 10 minutes after the
furnace purge.
Note that if the pilot flame
continues to fail after several
attempts, the boiler should be inspected to determine the fault and the
condition corrected.
Main Flame Light-Off
Once the pilot flame is
made, the
boiler control system opens the header block valves for the selected fuel.
A main flame light-off timer begins a 15 second countdown for natural gas, or 20
seconds for fuel oil, to establish and stabilize the main flame.
At 5 seconds before time out, the boiler control system closes the pilot block valves and opens the pilot vent
valve. The remaining 5 seconds are used to detect the main flame. For
the typical dual flame scanner design, a main flame failure shutdown is
initiated if both flame scanners return a “no flame” signal to the burner
control system. This will generate a boiler trip, and another furnace purge will be required. Once the
burner is lit, the system is in the NORMAL
RUN CONDITION and combustion controls should be released to
modulation control.
Shutdown
Per NFPA 8501, section
6-2.4.5, “The normal shutdown cycle for the boiler shall accomplish the
following in the order listed:
(a) Shut off fuel supply to the main burner.
(b) Interrupt spark and shut off fuel supply to igniter, if in
operation.
(c) For oil:
1. Where used, open the recirculating valve.
2. Shut off atomizing medium, if desired.
(d) For gas, vent piping between safety shutoff valves to
atmosphere.
(e) Perform a post purge of the boiler furnace enclosure.
(f) Shut down fan, if desired.”
For a safety shutdown,
a
manual reset is also required.
Normal
Boiler Shutdown
A normal shutdown is
initiated by operating BOILER SHUTDOWN switch. This will
initiate the shut down sequence listed above.
Boiler Master Fuel
Trip
Any of the following conditions
shall cause a boiler trip to occur. This results in the
shutdown of all fuel and requires another furnace purge cycle
before any attempt at re-lighting.
For
fuel oil:
1.
Excessive steam pressure.
2.
Low water level.
3. Low fuel pressure.
4.
Low oil temperature.
5. Loss of combustion air supply.
6. Loss of flame.
7.
Loss of control system power.
8. Loss of atomizing medium,
if used.
For
natural gas:
1. Excessive
steam pressure or water temperature.
2. Low water
level.
3. High or
low gas pressure.
4. Loss of
combustion air supply.
5. Loss of
flame.
6. Loss of
control system power.
In the event of an MFT, the
control system shall initiate the following:
1. Execute a shut down as listed above.
2.
Illuminate the appropriate indicator lights and alarms.
3. Return
the system to the pre-purge state
Boiler restart will be inhibited until all pre-purge requirements are satisfied.
Alarms
The following is a list of recommended alarm conditions:
1.
Any boiler or burner trip signal
2.
High or low water level
3.
High furnace pressure
4. Partial Loss of flame (For
the typical two scanner system, one indicates “no flame”)
5. Main fuel shutoff valves
closed
6. Loss of
control system power
7. Unsuccessful burner shutdown
Interface with the Combustion Control System (CCS)
The following list, at a minimum, of
signals should be sent to the Combustion Control System:
1. Controls to purge position
2. Controls to light-off position
3. Normal run condition: release controls to modulation
4. Main natural gas block valve open: permissive to place gas
control valve in automatic.
5. Master fuel trip: run boiler load to zero and place combustion
controls in manual.
6. Oil recirculation signal
Under the provisions of NFPA 8501,
section 6-5.2.3, for a single burner boiler, the BMS and CCS may reside in the same processor. This option
can to reduce the integration complexity and increase the BMS to CCS interface reliability.
Operator Interface
The
above describes a traditional operator interface using discrete
switches and indicator lights. The control
designer is encouraged to incorporate a graphical user interface or similar options
in order to enhance the ease of use and readability of the boiler
control system operator interface.
Endnotes:
[i] Prepurge permissives
condition checks and furnace purge are to be initiated by the operator from the local BMS panel (see NFPA 8501, Chapter 5 for detailed guidelines on cold starting using fuel
oil, Chapter 6 for cold starting using natural gas).
[ii] Purge air flow (NFPA 8501, section 6-2.4.1(h): The total furnace airflow shall
not be reduced below the purge rate
airflow (70% of the maximum continuous airflow capacity). Reducing
airflow below these limits will lead to a MFT, and a new furnace purge
will be required.
[iii]
Suggested color design:
Purge
Permissives indicating lights: |
white |
Purge
Available indicating light: |
green
|
Purge in
progress indicating light: |
amber |
Purge
complete indicating light: |
white
|
MFT reset
indicating light: |
red |
Article # 0005
TEST QUESTIONS:
1. The Burner Management System must be designed to ...?
-
provide a safe and orderly evacuation procedure
-
ensure a safe and orderly operating sequence
-
eliminate all possible errors by the operator
-
All of the above
2. The
BMS shall provide protection against most common emergencies but cannot replace
...?
-
an intelligent operators reasonable judgment
-
a
fully integrated plant control system
-
a
properly wired and located emergency shutdown switch.
-
All of the above
3. What
condition(s) must be satisfied prior to starting a furnace purge cycle?
-
The fuel valves must be proven closed
-
Air dampers are in the fully open position
-
All flame scanners reading "No Flame"
-
All of the above
4. What
may be used to interrupt the main flame start-up sequence after it has begun?
-
Activating the "Boiler Stop" or the "Emergency Stop" switch.
-
Blowing out the pilot light.
-
A call
from the Governor or the President.
-
All of the above
5. What
must be completed before any fuel firing is permitted?
-
The
boiler must be drained and filled with fresh water.
-
A
pre-fire inspection by the local fire department.
-
A
Certificate of Inspection must be issued by the state boiler inspector.
-
A satisfactory furnace purge cycle.
6. Which
of the following conditions will cause a boiler trip (MFT) to occur?
-
Excessive steam pressure
-
Loss
of combustion air supply
-
Low
water level
-
All of the above
7. The
Boiler Management System shall be designed to...?
-
monitor and control the correct component sequencing during start-up and
shut-down
-
allow for the unattended start-up and shut-down of the boiler
-
allow firing the boiler without a furnace purge being completed
-
All of the above
8. The
burner startup period timer is set for ...?
-
no more than 10 minutes
-
no
less than 10 minutes
-
30
seconds
-
to
between 20 and 40 minutes at the discretion of the operator
9.
As indicated in NFPA
8501, section 6-2.4.1(i), the purge shall be “...sufficient for at least
____ air changes” of the furnace.
-
eight
-
six
-
five
-
two
10. Which
of the following is a recommended alarm condition?
-
High
furnace pressure
-
A
boiler trip signal
-
loss
of control system power
-
All of the above
Take a Test Article Library
CEEJ Home Submit an Article Contact CEEJ